Certification
designation
Go to details
Ansul®, Inergen® 200 bar, inert gas total-flood type extinguishing system
|
Certification id: |
afp - 1262 |
Registered: 21-Dec-1999 |
Valid until: 30-Apr-2026 |
|
|
|
Version: 24 (8-Apr-2025) |
|
|
|||
|
Product type(s): |
0501: Gaseous Fire Extinguishing System Equipment and Components |
||||
|
Reference criteria: |
1. Australian Standard AS ISO 14520.1-2009, 'Gaseous fire-extinguishing systems - Physical properties and system design - General requirements (ISO 14520-1:2006, MOD)'. 2. Australian Standard AS ISO 14520.15-2009, 'Gaseous fire-extinguishing systems - Physical properties and system design - IG-541 extinguishant (ISO 14520-15:2005, MOD)'. |
||||
|
Agent/distributor: |
Tyco Fire Protection Products |
||||
|
Level 3, 37 Dalmore Drive, Caribbean Park, SCORESBY, VIC, AUSTRALIA, 3179 |
|||||
|
Ph.: 13 0072 5688 |
Fax: |
||||
|
Web site: https://www.tyco-fire.com |
Email/web addr.: info.aust@tycofp.com |
||||
|
Registrant: |
Tyco Fire Protection
Products |
||||
|
|
|
||||
|
|
|
||||
|
|
|
||||
|
Certificate
of Conformity: |
Ansul®, Inergen® 200 bar, inert gas total-flood type extinguishing system
|
ANSUL (Tyco) part num. |
Description |
Drawing num. (rev.) |
|
A01575011 |
Inergen Cyl. Assy. 200 bar ANZ. |
575011 (DB) |
|
(IGVAL200) |
Discharge Valve, Australian Version (ANSUL p/n 426679) |
426679(3) |
|
A01575018 |
Transport Cap |
575018 (CB) |
|
423684 |
Electric Actuator for CV-98 Discharge Valve (suits IGVAL200) |
423550(13) |
|
423309 |
Mechanical Actuator, Local Manual Type w/- Locking Pin, for CV-98 Discharge Valve |
423309(1) |
|
423310 |
Mechanical Actuator, Local Manual Type w/o Locking Pin, for CV-98 Discharge Valve |
|
|
423311 |
Mechanical Actuator, Remote Cable-pull Type, for CV-98 Discharge Valve |
423311(2) |
|
423568 |
Discharge Hose Assembly c/w check (200 bar) |
423568(1) |
|
831809 |
Stainless Steel Actuation Hose Assembly, 406 long. |
|
|
832335 |
Stainless Steel Actuation Hose Assembly, 508 long. |
|
|
832336 |
Stainless Steel Actuation Hose Assembly, 609 long. |
|
|
(IGORIF025) |
Pressure Reducing Orifice Assembly, 25NB, ANSUL p/n 416679 |
|
|
(IGORIF032) |
Pressure Reducing Orifice Assembly, 32NB, ANSUL p/n 416680 |
|
|
(IGORIF040) |
Pressure Reducing Orifice Assembly, 40NB, ANSUL p/n 416681 |
|
|
(IGORIF050) |
Pressure Reducing Orifice Assembly, 50NB, ANSUL p/n 416682 |
|
|
(IGNOZ015) |
Discharge Nozzle, 360° pattern, 15NB, ANSUL p/n 417362 |
|
|
(IGNOZ025) |
Discharge Nozzle, 360° pattern, 20NB, ANSUL p/n 417364 |
|
|
(IGNOZ032) |
Discharge Nozzle, 360° pattern, 32NB, ANSUL p/n 417365 |
|
|
(IGNOZ040) |
Discharge Nozzle, 360° pattern, 40NB, ANSUL p/n 417366 |
|
|
(IGNOZ050) |
Discharge Nozzle, 360° pattern, 50NB, ANSUL p/n 426155 |
|
|
(IGNOZ065) |
Discharge Nozzle, 360° pattern, 65NB, ANSUL p/n 426156 |
|
|
(IGNOZ080) |
Discharge Nozzle, 360° pattern, 80NB, ANSUL p/n 426137 |
|
|
(IGNOZS15) |
Discharge Nozzle, 180° pattern, 15NB, ANSUL p/n 426140 |
|
|
(IGNOZS25) |
Discharge Nozzle, 180° pattern, 25NB, ANSUL p/n 426142 |
|
|
(IGNOZS32) |
Discharge Nozzle, 180° pattern, 32NB, ANSUL p/n 426143 |
|
|
(IGNOZS40) |
Discharge Nozzle, 180° pattern, 40NB, ANSUL p/n 426157 |
|
|
(IGNOZS50) |
Discharge Nozzle, 180° pattern, 50NB, ANSUL p/n 426144 |
|
|
(IGNOZS65) |
Discharge Nozzle, 180° pattern, 65NB, ANSUL p/n 426145 |
|
|
(IGNOZS80) |
Discharge Nozzle, 180° pattern, 80NB, ANSUL p/n 426146 |
|
|
417708 |
Deflector Shield, Discharge Nozzle, 15NB |
|
|
417714 |
Deflector Shield, Discharge Nozzle, 25NB |
|
|
805156 |
Pressure Trip |
|
|
423923 |
Cylinder Pressure Test Assembly |
|
|
840309 |
Header Vent Plug |
|
|
842175 |
Pressure Bleeder Plug |
|
|
(73AEB03177) |
Cylinder Front Bracket |
|
|
(73AEB03207) |
Cylinder Rear Bracket |
|
|
431069 |
ANSUL® INERGEN® System Design, Installation, Recharge and Maintenance Manual, (with Australian Addendum) |
Revision March 1, 2006 |
|
427991 |
ANSUL® INERGEN® 200 bar Flow calculation software |
Ver. 4.4.5 1 Nov, 2011 |
Piping requirements:
Two types of piping shall be used in an Ansul®, Inergen® 200 bar, inert gas total-flood type extinguishing system:
1. High pressure piping, extending from the storage cylinders to the pressure reducing orifice. This shall be suitable for a working pressure of at least 23.5 MPa and shall be Class 2 or 3, Pipe Grade B, in accordance with AS 4041. Minimum thickness of pipe wall shall be in accordance with AS 4041. Welding shall be by Qualified Welders only. Welded flanges shall be to ANSI/ASME B16.5 Class 900 lb, AS 2129 Table T. Butt-welded fittings shall be to ANSI/ASME B16.9 or BS 1640 Classes 1 and 2 (Standard weight = Schedule 40. Extra strong = Schedule 80). Screwed fittings shall be DN50 maximum, and shall be 3000 lb fittings to BS 3799 or ANSI B16.11.
2. Low pressure piping, extending from the pressure reducing orifice to the nozzles. This shall be suitable for a working pressure of at least 11.5 MPa and shall be Class 2 or 3, Pipe Grade B, in accordance with AS 4041. Minimum thickness of pipe wall shall be in accordance with BS 1600 and ANSI/ASME B36.10M. Welding shall be by Certified Code Welders only. Welded flanges shall be to ANSI/ASME B16.5 Class 600 lb, AS 2129 Table K. Butt welded fittings shall be to ANSI/ASME B16.9 or BS 1640 Classes 1 and 2 (Standard weight = Schedule 40; Extra strong = Schedule 80). Screwed fittings shall be DN100 maximum, and shall be 3000 lb fittings to BS 3799 or ANSI B16.11.